184 Parameters
Emergency ramp
supervision delay
is set to 0%,
this parameter defines the maximum time an emergency stop
(mode Off1 or Off3) is allowed to take. If the motor has not
stopped when the time elapses, the drive trips on
, sets bit 8 of
, and coasts to a stop.
is set to a value other than 0%, this parameter
defines a delay between the receipt of the emergency stop
command and the activation of the supervision. It is
recommended to specify a short delay to allow the speed
change rate to stabilize.
0 s
0…100 s
Maximum ramp-down time, or supervision activation delay.
1 = 1 s
Temporarily suppresses auxiliary fan faults.
Certain drive types (especially those protected to IP55) have
an auxiliary fan built into the front cover as standard. If the fan
is stuck or disconnected, the control program generates a
fault (
If it is necessary to operate the drive without the front cover
(for example, during commissioning), this parameter can be
activated to temporarily generate a warning (
) instead of the fault.
Notes:
• The parameter must be activated within 2 minutes of drive
reboot (either by cycling the power or by parameter
).
• The parameter will be in effect until the auxiliary fan is
reconnected and detected, or until the next control unit
reboot.
Off
Normal operation, Aux fan supervision generates a fault.
0
Temporarily
bypassed
The auxiliary fan fault is temporarily replaced by a warning
indication.
The setting will revert automatically to
1
32
Configuration of signal supervision functions 1…6.
Six values can be chosen to be monitored; a warning or fault
is generated whenever predefined limits are exceeded.
See also section
(page
Signal supervision status word.
Indicates whether the values monitored by the signal
supervision functions are within or outside their respective
limits.
Note:
This word is independent of the drive actions defined
.
0000b
0000h…FFFFh
Signal supervision status word.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Supervision 1 active
is outside its limits.
1
Supervision 2 active
is outside its limits.
2
Supervision 3 active
is outside its limits.
3
Supervision 4 active
is outside its limits.
4
Supervision 5 active
is outside its limits.
5
Supervision 6 active
is outside its limits.
6…15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...