Parameters 173
Defines the high limit for critical frequency 3.
Note:
This value must be greater than or equal to the value of
0.00 Hz
-500.00…500.00
Hz
High limit for critical frequency 3.
See par.
Defines acceleration time 1 as the time required for the
frequency to change from zero to the frequency defined by
parameter
. After this frequency has
been reached, the acceleration continues with the same rate
to the value defined by parameter
.
If the reference increases faster than the set acceleration
rate, the motor will follow the acceleration rate.
If the reference increases slower than the set acceleration
rate, the motor frequency will follow the reference.
If the acceleration time is set too short, the drive will
automatically prolong the acceleration in order not to exceed
the drive torque limits.
5.0 s
0.000…1800.000 s
Acceleration time 1.
10 = 1 s
Defines deceleration time 1 as the time required for the
frequency to change from the frequency defined by
parameter
(
not
from parameter
) to zero.
If there is any doubt about the deceleration time being too
short, ensure that DC overvoltage control (
) is on.
Note:
If a short deceleration time is needed for a high inertia
application, the drive should be equipped with braking
equipment such as a brake chopper and brake resistor.
5.0 s
0.000…1800.000 s
Deceleration time 1.
10 = 1 s
Selects a source that forces the frequency reference to zero.
0 = Force frequency reference to zero
1 = Normal operation
Active
0.
0
Inactive
1.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
). -
Defines the shape of acceleration ramp at the beginning of
acceleration.
0.000
0.000...1800.000 s
Shape time 1.
10 = 1 s
Displays the frequency reference after selection (
). See the control chain diagram on page
This parameter is read-only.
-
-500.00
…500.00 Hz
Frequency reference after selection.
See par.
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...