82 Program features
Voltage control and trip limits
The control and trip limits of the intermediate DC voltage regulator are relative to the
supply voltage as well as drive/inverter type. The DC voltage (
U
DC
) is approximately
1.35 times the line-to-line supply voltage, and is displayed by parameter
.
The following table shows the values of selected DC voltage levels. Note that the
absolute voltages vary according to the drive/inverter type and AC supply voltage
range.
Settings
Parameters
(page
),
),
) and
(page
DC voltage level [V]
See
AC supply voltage range [V]
380…415
AC supply voltage range [V]
440…480
Overvoltage fault limit
840
840
Overvoltage control limit
780
780
Internal brake chopper start limit
780
780
Internal brake chopper stop limit
760
760
Overvoltage warning limit
745
745
Undervoltage warning limit
value
1)
0.85×1.41×par
value
1)
0.85×1.41×380 = 455
2)
0.85×1.41×440 = 527
2)
Undervoltage control limit
value
1)
0.75×1.41×par
value
1)
0.75×1.41×380 = 402
2)
0.75×1.41×440 = 465
2)
Charging relay closing limit
value
1)
0.75×1.41×par
value
1)
0.75×1.41×380 = 402
2)
0.75×1.41×440 = 465
2)
Charging relay opening limit
value
1)
value
1)
0.65×1.41×380 = 348
2)
0.65×1.41×440 = 403
2)
DC voltage at upper bound of supply
voltage range (
U
DCmax
)
560
648
DC voltage at lower bound of supply
voltage range (
U
DCmin
)
513
594
Charging activation/standby limit
3)
value
1)
0.65×1.41×par
value
1)
0.65×1.41×380 = 348
2)
0.65×1.41×440 = 403
2)
Undervoltage fault limit
value
1)
0.45×1.41×par
value
1)
0.45×1.41×380 = 241
2)
0.45×1.41×440 = 279
2)
1)
If parameter
is set to
and
set to
is used,
2)
otherwise the lower limit of the range selected with parameter
is used.
3)
When standby is activated, drive modulation is stopped, the fan is stopped and the pre-charge circuit is
activated. If the voltage exceeds this level again, the drive has to complete charging before it will
automatically continue operation.
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...