24 Start-up, control with I/O and ID run
Check that AI is scaled correctly for the control
mode in use. In speed control mode, check that
= 1500 or 1800 rpm.
In scalar control mode, check
= 50 or 60 Hz.
Select the type of ID run you want to do and
press
(
Select
) (or
).
Check the motor limits shown on the panel. If you
need other limits during the ID run you can enter
them here. The originals limits will be restored
after the ID run, unless you select
Set values as
permanent
.
Press the Hand key
(
)
to start the ID run.
In general, it is recommended not to press any
control panel keys during the ID run. However,
you can stop the ID run at any time by pressing
the Off key
(
)
.
During the ID run a progress view is shown.
After the ID run is completed, text
ID run done
is
shown. The LED stops blinking.
If the ID run fails, fault
chapter
on page
for more
information.