14 Start-up, control with I/O and ID run
How to start up the drive
How to start up the drive using First start assistant on the Hand-Off-
Auto control panel
Safety
Do not start-up the drive unless you are a qualified electrician.
Read and obey the instructions in chapter
Safety instructions
at the beginning of the
Hardware manual
of the drive. Ignoring the instructions can cause physical injury or death, or
damage to the equipment
Check the installation. See chapter
Installation checklist
in the
Hardware manual
of the
drive.
Make sure there is no active start on (DI1 in factory settings, that is, Water default
configuration). The drive will start up automatically at power-up if the external run
command is on and the drive is in the external control mode.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine
if
• there is a risk of damage in case of an incorrect direction of rotation, or
• a
Normal
ID run is required during the drive start-up, when the load torque is higher
than 20% or the machinery is not able to withstand the nominal torque transient during
the ID run.
Hints on using the assistant control panel
The two commands at the bottom of the display
(
Options
and
Menu
in the figure on the right),
show the functions of the two softkeys
and
located below the display. The commands
assigned to the softkeys vary depending on the
context.
Use keys
,
,
and
to move the cursor
and/or change values depending on the active
view.
Key shows a context-sensitive help page.
For more information, see
ACS-AP-x assistant
control panels user’s manual
(3AUA0000085685
[English]).
?
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...