182 Parameters
Selects how the drive reacts to a motor stall condition.
A stall condition is defined as follows:
• The drive exceeds the stall current limit (
, and
• the output frequency is below the level set by parameter
or the motor speed is below the
• the conditions above have been true longer than the time
set by parameter
.
No action
None (stall supervision disabled).
0
Warning
The drive generates an
warning.
1
Fault
The drive trips on fault
2
Stall current limit in percent of the nominal current of the
motor. See parameter
200.0%
0.0…1600.0%
Stall current limit.
-
Stall speed limit in rpm. See parameter
150.00 rpm;
180.00 rpm
(
0.00…10000.00
rpm
Stall speed limit.
See par.
Stall frequency limit. See parameter
Note:
Setting the limit below 10 Hz is not recommended.
15.00 Hz;
18.00 Hz
(
0.00…1000.00 Hz
Stall frequency limit.
See par.
Stall time. See parameter
20 s
0…3600 s
Stall time.
-
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...