344 Fault tracing
A6A5
No motor data
Parameters in group 99 have
not been set.
Check that all the required parameters
in group 99 have been set.
Note:
It is normal for this warning to
appear during the start-up and continue
until the motor data is entered.
A6A6
Voltage category
unselected
The voltage category has not
been defined.
Set voltage category in parameter
A6A7
System time not set
System time is not set. Timed
functions cannot be used and
fault log dates are not correct.
Set the system time manually or
connect the panel to the drive to
synchronize the clock. If basic panel is
used, synchronize the clock through the
EFB or a fieldbus module.
Set parameter
to
to disable the
timed functions if they are not used.
A6B0
User lock is open
The user lock is open, ie. user
lock configuration parameters
are visible.
Close the user lock by entering an
invalid pass code in parameter
. See section
(page
).
A6B1
User pass code not
confirmed
A new user pass code has
been entered in parameter
but not confirmed in
Confirm the new pass code by entering
the same code in
. To cancel,
close the user lock without confirming
the new code. See section
(page
).
A6D1
FBA A parameter
conflict
The drive does not have a
functionality requested by a
PLC, or requested functionality
has not been activated.
Check PLC programming.
Check settings of parameter groups
.
A6E5
AI parametrization
The current/voltage hardware
setting of an analog input does
not correspond to parameter
settings.
Check the event log for an auxiliary
code. The code identifies the analog
input whose settings are in conflict.
Adjust either the hardware setting (on
the drive control unit) or parameter
.
Note:
Control board reboot (either by
cycling the power or through parameter
) is required to
validate any changes in the hardware
settings.
A6E6
ULC configuration
User load curve configuration
error.
Check the auxiliary code (format XXXX
ZZZZ). “ZZZZ” indicates the problem
(see actions for each code below).
0000 Speed points inconsistent.
Check that each speed point
(parameters
) has a
higher value than the previous point.
0001 Frequency points inconsistent. Check that each frequency point
) has a higher value than
the previous point.
0002 Underload point above
overload point.
Check that each overload point
(
) has a higher value than
the corresponding underload point
(
).
0003 Overload point below
underload point.
Code
(hex)
Warning / Aux. code Cause
What to do
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...