Parameters 211
Warning/Fault
The drive generates a warning (
) if the signal stays continuously below the underload
curve for half of the time defined by parameter
The drive trips on
if the signal stays
continuously above the underload curve for a time defined by
parameter
3
Defines the first of the five speed points on the X-axis of the
user load curve.
Speed points are used if parameter
is set to
or if
is set to
and the reference unit is rpm.
The five points must be in order from lowest to highest. The
points are defined as positive values, but the range is
symmetrically effective also in the negative direction. The
monitoring is not active outside these two areas.
150.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the second speed point.
See parameter
.
750.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the third speed point.
See parameter
.
1290.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the fourth speed point.
See parameter
.
1500.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the fifth speed point.
See parameter
.
1800.0 rpm
-30000.0…30000.0
rpm
Speed.
1 = 1 rpm
Defines the first of the five frequency points on the X-axis of
the user load curve.
Frequency points are used if parameter
is set to
and the reference unit is Hz.
The five points must be in order from lowest to highest. The
points are defined as positive values, but the range is
symmetrically effective also in the negative direction. The
monitoring is not active outside these two areas.
5.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
Defines the second frequency point.
See parameter
.
25.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
Defines the third frequency point.
See parameter
.
43.0 Hz
-500.0…500.0 Hz
Frequency.
1 = 1 Hz
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...