104 Parameters
Drive output power. The unit is selected by parameter
. A filter time constant for this signal can be
-
-32768.00…
32767.00 kW or hp
Output power.
1 = 1 unit
Output power in percent of the nominal motor power.
-
-300.00… 300.00%
Output power.
1 = 1%
Output power in percent of the nominal drive power.
-
-300.00… 300.00%
Output power.
1 = 1%
Estimated mechanical power at motor shaft.
-
-32768.00…
32767.00 kW or hp
Motor shaft power.
1 = 1 unit
Amount of energy that has passed through the drive (in either
direction) in full gigawatt-hours. The minimum value is zero.
-
0…65535 GWh
Energy in GWh.
1 = 1 GWh
Amount of energy that has passed through the drive (in either
direction) in full megawatt-hours. Whenever the counter rolls
over,
is incremented. The
minimum value is zero.
-
0…1000 MWh
Energy in MWh.
1 = 1 MWh
Amount of energy that has passed through the drive (in either
direction) in full kilowatt-hours. Whenever the counter rolls
over,
is incremented. The
minimum value is zero.
-
0…1000 kWh
Energy in kWh.
10 = 1 kWh
Used flux reference in percent of nominal flux of motor.
-
0…200%
Flux reference.
1 = 1%
Torque that corresponds to 100% of nominal motor torque.
The unit is selected by parameter
.
Note:
This value is copied from parameter
if entered. Otherwise the value is calculated
from other motor data.
-
0.000…4000000
N·m or lb·ft
Nominal torque.
1 = 100 unit
Ambient temperature of the drive. Only for drive frames R6 or
larger.
-
40.0…120.0 °C or °F Temperature.
1 = 1 °
Current hour energy consumption. This is the energy of the
last 60 minutes (not necessarily continuous) the drive has
been running, not the energy of a calendar hour.
If the power is cycled, after the drive is again up and running,
the parameter value is set to the value it had before the power
cycle.
-
0.00… 1000000.00
kWh
Energy.
1 = 1 kWh
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...