Parameters 113
Start inhibit status word. This word specifies the source of the
inhibiting signal that is preventing the drive from starting.
The conditions marked with an asterisk (*) only require that
the start command is cycled. In all other instances, the
inhibiting condition must be removed first.
See also parameter
, bit 1.
This parameter is read-only.
Note:
At the moment the software does not work as it should.
Now bit 5 never changes state, and Start interlock changes bit
6 state, not bit 4 bit state. This will be corrected in the next
software version.
-
0000h…FFFFh
Start inhibit status word.
1 = 1
Speed control status word.
This parameter is read-only.
-
0000h…FFFFh
Speed control status word.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Not ready run
1 = DC voltage is missing or drive has not been parametrized
correctly. Check the parameters in groups 95 and 99.
1
Ctrl location changed
* 1 = Control location has changed
2
SSW inhibit
1 = Control program is keeping itself in inhibited state
3
Fault reset
* 1 = A fault has been reset
4
Start interlocked
1 = Start interlocked
5
Run permissive
1 = Run permissive signal missing
6
Reserved
7
STO
1 = Safe torque off function active
8
Current calibration
ended
* 1 = Current calibration routine has finished
9
ID run ended
* 1 = Motor identification run has finished
10
Reserved
11
Em Off1
1 = Emergency stop signal (mode off1)
12
Em Off2
1 = Emergency stop signal (mode off2)
13
Em Off3
1 = Emergency stop signal (mode off3)
14
Auto reset inhibit
1 = The autoreset function is inhibiting operation
15
Reserved
Bit
Name
Description
0
Zero speed
1 = Drive has been running below zero speed limit (par.
)
for a time defined by parameter
1
Forward
1 = Drive is running in forward direction above zero speed limit
(par.
)
2
Reverse
1 = Drive is running in reverse direction above zero speed limit
(par.
)
3…6
Reserved
7
Any constant speed
request
1 = A constant speed or frequency has been selected; see par.
.
8…15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...