Parameters 207
DC voltage
7
Output power
(page
). 8
Reserved
9
Speed ref ramp in
(page
).
10
Speed ref ramp out
11
Speed ref used
).
12
Reserved
13
Freq ref used
14
Reserved
15
Process PID out
(page
16
). -
Peak value logger filtering time. See parameter
2.00 s
0.00…120.00 s
Peak value logger filtering time.
100 = 1 s
Selects the signal to be monitored by amplitude logger 2. The
signal is sampled at 200 ms intervals.
The results are displayed by parameters
. Each
parameter represents an amplitude range, and shows what
portion of the samples fall within that range.
The signal value corresponding to 100% is defined by
parameter
.
Amplitude logger 2 can be reset using parameter
. The logger is also reset whenever the signal
source or scaling is changed. The date and time of the last
reset are stored into parameters
respectively.
For the selections, see parameter
Defines the signal value that corresponds to 100% amplitude. 100.00
0.00…32767.00
Signal value corresponding to 100%.
1 = 1
Resets the peak value logger and/or amplitude logger 2.
(Amplitude logger 1 cannot be reset.)
Done
Reset completed or not requested (normal operation).
0
All
Reset both the peak value logger and amplitude logger 2.
1
PVL
Reset the peak value logger.
2
AL2
Reset amplitude logger 2.
3
Peak value recorded by the peak value logger.
0.00
-32768.00…
32767.00
Peak value.
1 = 1
The date on which the peak value was recorded.
01.01.1980
-
Peak occurrence date.
-
The time at which the peak value was recorded.
00:00:00
-
Peak occurrence time.
-
Motor current at the moment the peak value was recorded.
0.00 A
-32768.00…
32767.00 A
Motor current at peak.
1 = 1 A
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...