220 Parameters
Freezes, or defines a source that can be used to freeze, the
setpoint of the process PID controller. This feature is useful
when the reference is based on a process feedback
connected to an analog input, and the sensor must be
serviced without stopping the process.
1 = Process PID controller setpoint frozen
See also parameter
.
Not selected
Process PID controller setpoint not frozen.
0
Selected
Process PID controller setpoint frozen.
1
DI1
Digital input DI1 (
, bit 0).
2
DI2
Digital input DI2 (
, bit 1).
3
DI3
Digital input DI3 (
, bit 2).
4
DI4
Digital input DI4 (
, bit 3).
5
DI5
Digital input DI5 (
, bit 4).
6
DI6
Digital input DI6 (
, bit 5).
7
Reserved
8…17
Timed function 1
18
Timed function 2
19
Timed function 3
20
Supervision 1
21
Supervision 2
22
Supervision 3
23
Source selection (see
). -
Inverts the input of the process PID controller.
0 = Deviation not inverted (Deviation = Setpoint - Feedback)
1 = Deviation inverted (Deviation = Feedback - Setpoint)
See also section
Sleep and boost functions for process PID
(page
).
Not inverted
(Ref - Fbk)
0.
0
Inverted (Fbk - Ref) 1.
1
Source selection (see
). -
Defines the gain for the process PID controller. See
parameter
.
1.00 s
0.10…100.00
Gain for PID controller.
100 = 1
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...