Parameters 117
10
Configuration of digital inputs and relay outputs.
Displays the status of digital inputs DI1…DI6. Bits 0…5 reflect
the delayed status of DI1…DI6.
Example:
0000000000010011b = DI5, DI2 and DI1 are on,
DI3, DI4 and DI6 are off.
This word is updated only after a 2 ms activation/deactivation
delay. When the value of a digital input changes, it must
remain the same in two consecutive samples, that is for 2 ms,
for the new value to be accepted.
This parameter is read-only.
-
0000h…FFFFh
Delayed status for digital inputs.
1 = 1
The electrical statuses of the digital inputs can be overridden
for eg. testing purposes. A bit in parameter
is provided for each digital input, and its value is applied
whenever the corresponding bit in this parameter is 1.
Note:
Boot and power cycle reset the force selections
(parameters
).
0000h
0000h…FFFFh
Override selection for digital inputs.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
DI1
1 = Digital input 1 is ON.
1
DI2
1 = Digital input 2 is ON.
2
DI3
1 = Digital input 3 is ON.
3
DI4
1 = Digital input 4 is ON.
4
DI5
1 = Digital input 5 is ON.
5
DI6
1 = Digital input 6 is ON.
6…15
Reserved
Bit
Value
0
1 = Force DI1 to value of bit 0 of parameter
. (0 = Normal mode)
1
1 = Force DI2 to value of bit 1 of parameter
. (0 = Normal mode)
2
1 = Force DI3 to value of bit 2 of parameter
. (0 = Normal mode)
3
1 = Force DI4 to value of bit 3 of parameter
. (0 = Normal mode)
4
1 = Force DI5 to value of bit 4 of parameter
. (0 = Normal mode)
5
1 = Force DI6 to value of bit 5 of parameter
. (0 = Normal mode)
6…15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...