166 Parameters
Defines the derivation time of the speed controller. Derivative
action boosts the controller output if the error value changes.
The longer the derivation time, the more the speed controller
output is boosted during the change. If the derivation time is
set to zero, the controller works as a PI controller, otherwise
as a PID controller. The derivation makes the control more
responsive for disturbances. For simple applications,
derivative time is not normally required and should be left at
zero.
The speed error derivative must be filtered with a low pass
filter to eliminate disturbances.
The figure below shows the speed controller output after an
error step when the error remains constant.
0.000 s
0.000…10.000 s
Derivation time for speed controller.
1000 = 1 s
Defines the derivation filter time constant. See parameter
.
8 ms
0…10000 ms
Derivation filter time constant.
1 = 1 ms
Defines the proportional gain for the speed controller when an
emergency stop is active. See parameter
10.00
1.00…250.00
Proportional gain upon an emergency stop.
100 = 1
Displays the output of the proportional (P) part of the speed
controller. See the control chain diagram on page
.
This parameter is read-only.
-
-30000.0…
30000.0%
P-part output of speed controller.
See par.
Displays the output of the integral (I) part of the speed
controller. See the control chain diagram on page
.
This parameter is read-only.
-
-30000.0…
30000.0%
I-part output of speed controller.
See par.
No.
Name/Value
Description
Def/FbEq16
Gain = K
p
= 1
T
I
= Integration time > 0
T
D
= Derivation time > 0
T
s
= Sample time period = 250 µs
Δ
e = Error value change between two samples
K
p
×
T
D
×
Δ
e
T
s
Controller output
e = Error value
Error value
Time
T
I
K
p
× e
K
p
× e
%
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...