350 Fault tracing
D510
Inlet minimum
pressure
Programmable warning:
Measured inlet pressure is
below the defined warning
level.
Check the pump inlet for blockages or
closed valve.
Check the configuration of inlet
pressure protection.
See parameters
minimum pressure warning level
.
Code
(hex)
Warning / Aux. code Cause
What to do