210 Parameters
37
Settings for user load curve.
See also section
User load curve (Condition monitoring)
(page
Displays the status of the monitored signal. The status is
shown only while the drive is running. (The status word is
independent of the actions and delays selected by
parameters
.)
This parameter is read-only.
0000h
0000h…FFFFh
Status of the monitored signal.
1 = 1
Selects the signal to be monitored. The function compares
the absolute value of the signal against the load curve.
Not selected
No signal selected (monitoring disabled).
0
Motor speed %
(page
).
1
Motor current %
2
Motor torque %
(page
).
3
Output power % of
motor nominal
(page
4
Output power % of
drive nominal
(page
).
5
Source selection (see
). -
Selects how the drive reacts if the absolute value of the
monitored signal stays continuously above the overload curve
for longer than the value of
.
Disabled
No action taken.
0
Warning
The drive generates a warning (
).
1
Fault
.
2
Warning/Fault
The drive generates a warning (
if the signal stays continuously above the overload curve for
half of the time defined by parameter
if the signal stays
continuously above the overload curve for a time defined by
parameter
3
Selects how the drive reacts if the absolute value of the
monitored signal stays continuously above the overload curve
for longer than the value of
Disabled
No action taken.
0
Warning
The drive generates a warning (
).
1
Fault
2
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Under load limit
1 = Signal lower than the underload curve.
1
Within load range
1 = Signal between the underload and overload curve.
2
Overload limit
1 = Signal higher than the overload curve.
3…15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...