The MLC 9000+ is a DIN-rail-mounted multi-
loop PID control system that can be connected 
to a variety of fieldbus systems.  The MLC 
9000+ system consists of a single Bus Module 
and any combination of up to 8 Loop Modules.   
 
The Bus Module is a supervisory module 
connected directly to the DIN rail. It provides 
power to the Loop Modules and contains a 
back-up of the system configuration data. It 
also manages the communications with 
external devices. 
 
The Loop Modules are independent control 
modules managed by the Bus Module. They are connected to the DIN rail via an inter-
connect module that provides power and communications from the Bus Module. Any 
combination of Loop Module types can be connected to the Bus Module, as long as the 
maximum of eight modules is not exceeded. 
 
 
Remove the Bus Module and Loop Modules from there packing and install them as 
described in their installation manuals. Connect the configuration cable supplied with the 
MLC 9000+ Workshop software to the RJ11 port of the Bus Module and to the RS 232 port 
of the PC. The MLC 9000+ is now ready for configuration. (More information on the 
hardware installation can be found in the MLC 9000+ User Guide) 
 
 
 
1.  Insert the installation disk into the CD drive on your PC. The Set-up program should 

start automatically; If it does not, navigate to the appropriate drive using Windows 
Explorer and double click the Set-up icon. 

2.  The Set-up Wizard will guide you through the installation procedure. 
3.  You will be prompted to define a folder into which you want the Configurator installed. 

You may use the default folder or specify one of your own choice. 

 
 
 
The first screen displayed on start-up is an options menu. This options menu gives you 
three choices: 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 

1. 

Create a new System Configuration:

  This option is for configuration of an MLC 

9000+ system without the physical hardware being connected to the PC. 

2. 

Load an existing System Configuration from the disk:

  This option loads a 

configuration that has already been saved previously. 

3. 

Upload System Configuration from a connected device:

  This option gathers 

the system configuration information from an MLC 9000+ system that is 
connected to the RS 232 port of the PC. 

 

To create a new configuration select ‘Create a new System Configuration’ and press Start, 
this will then take you to the system configuration screen. If the Bus Module is new and has 
never been configured this option must be selected as the Bus module will have no 
configuration. 

 

To navigate through the different configuration screens of the MLC 9000+ Workshop 
software select View in the menu bar or use the buttons in the task bar. 
 
 
 
 

 
 
The system configuration 
screen is used to define which 
Bus Module and Loop Modules 
are used in the MLC 9000+ 
system.  
The Left hand column is a list 
of all the Bus Module and Loop 
Module drivers available. The 
right hand column is a blank 
system. To insert a module into 
the system drag from the 
available modules in the left 
hand column and drop in an 
available slot in the right hand 
column. The first module to 
add is the Bus Module. Select 
a Bus Module type and drag 
and drop it into the Bus Module 

slot. The Loop Modules can 
then be added in any order. 
When adding modules ensure 
that the physical hardware is 
installed in the same 
configuration. For example if the 
physical MLC 9000+ system is a 
BM230-DN Bus Module and 
three Z3611 Loop Modules the 
system configuration entered 
must be the same. 
 
Once System Configuration is 
complete proceed to the 
Configuration Wizard using the 
View | Configuration wizards 
menu option or by pressing the 

wizard button. 

 

 
 
 
The configuration wizard 
screen is used to 
configure the control 
characteristics of the 
LCMs and the standard 
communication 
parameters of the Bus 
Module. In the left hand 
column are all the 
modules that were 
added during System 
Configuration.  
 
Click on the + sign next 
to the module. A list of 
the available 
configuration wizards is 
then displayed. To 
activate a wizard double 
click on the wizard 
name. 

 
 
 
 
 
 
 
Each Bus Module type has a wizard that can 
be used to configure the communication 
parameters required for successful 
communication. 
 
 
 
 

 
All Loop Modules have three common wizards: 
 

1. Loop Configuration:

 This wizard is for 

configuration of the most common control 
loop parameters in the module. 

  

 
 
 
For single loop controller modules (Z1200, 
Z1300, and Z1301) the loop configuration only 
gives you the option to configure a single loop. 
 
 
 
 
 

 
 
 
For multi-loop controller modules (Z3611, 
Z3621, Z4610 and Z4620) the loop 
configuration gives you the option to 
configure multiple loops with the same 
configuration at the same time. This then 
reduces the time required to configure 
multiple loops. 
 
 

 
 

 
 
2. Output Configuration: 

This wizard is 

used to allocate the outputs to specific 
tasks and in the case of the multi-loop 
Loop Modules which loop they will work 
with.

 

 
 
Any of the outputs in a single loop module 
can be assigned any task. For multiple loop 

modules each control loop needs to be 
assigned an output. 
 
 
 
 

3. Loop Calibration: 

This wizard is for 

calibration of the inputs. It should only be 
used if you are sure that the input is out of 
calibration.

 

 
WARNING: 

Incorrect calibration will cause the 

MLC 9000+ to malfunction 

 
 

 
 
 

For modules that have the Heater Current input (Z1301, Z3611 and Z3621) there is a 
separate wizard 
 
 
 
 

 
 
 
 
 
 
 
 
 

1. HARDWARE INSTALLATION 

MLC 9000+ Quick Start Guide 59328-1 

Figure 1 – A Typical MLC 9000+ 

System 

2. INSTALLING MLC 9000+ WORKSHOP 

3. RUNNING MLC 9000+ WORKSHOP 

4. SYSTEM CONFIGURATION 

5. CONFIGURATION WIZARDS 

Отзывы: