386 Fieldbus control through the embedded fieldbus interface (EFB)
Coils (0xxxx reference set)
Coils are 1-bit read/write values. Control Word bits are exposed with this data type.
The table below summarizes the Modbus coils (0xxxx reference set). Note that the
references are 1-based index which match the address transmitted on the wire.
Reference ABB Drives profile
DCU Profile
000001
OFF1_CONTROL
STOP
000002
OFF2_CONTROL
START
000003
OFF3_CONTROL
Reserved
000004
INHIBIT_OPERATION
Reserved
000005
RAMP_OUT_ZERO
RESET
000006
RAMP_HOLD
EXT2
000007
RAMP_IN_ZERO
RUN_DISABLE
000008
RESET
STOPMODE_RAMP
000009
Not for ACH580/ACQ580
STOPMODE_EMERGENCY_RAMP
000010
Not for ACH580/ACQ580
STOPMODE_COAST
000011
REMOTE_CMD
Reserved
000012
EXT_CTRL_LOC
RAMP_OUT_ZERO
000013
USER_0
RAMP_HOLD
000014
USER_1
RAMP_IN_ZERO
000015
USER_2
Reserved
000016
USER_3
Reserved
000017
Reserved
FB_LOCAL_CTL
000018
Reserved
FB_LOCAL_REF
000019
Reserved
Reserved
000020
Reserved
Reserved
000021
Reserved
Reserved
000022
Reserved
Reserved
000023
Reserved
USER_0
000024
Reserved
USER_1
000025
Reserved
USER_2
000026
Reserved
USER_3
000027
Reserved
Reserved
000028
Reserved
Reserved
000029
Reserved
Reserved
000030
Reserved
Reserved
000031
Reserved
Reserved
000032
Reserved
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...