374 Fieldbus control through the embedded fieldbus interface (EFB)
5
EXT2
1
Select External control location EXT2. Effective if the
control location is parameterized to be selected from the
fieldbus.
0
Select External control location EXT1. Effective if the
control location is parameterized to be selected from the
fieldbus.
6
RUN_DISABLE
1
Run disable. If the drive is set to receive the run enable
signal from the fieldbus, this bit deactivates the signal.
0
Run enable. If the drive is set to receive the run enable
signal from the fieldbus, this bit activates the signal.
7
STOPMODE_RA
MP
1
Normal ramp stop mode
0
(no op) Default to parameter stop mode if bits 7…9 are all
0.
8
STOPMODE_EM
ERGENCY_RAM
P
1
Emergency ramp stop mode.
0
(no op) Default to parameter stop mode if bits 7…9 are all
0.
9
STOPMODE_CO
AST
1
Coast stop mode.
0
(no op) Default to parameter stop mode if bits 7…9 are all
0.
10
RAMP_PAIR _2
1
(no op)
0
Select ramp set 1 (Acceleration time 1 / Deceleration time
1).
11
RAMP_OUT_ZER
O
1
Force Ramp Function Generator output to zero. Drive
ramps to stop (current and DC voltage limits in force).
0
Normal operation.
12
RAMP_HOLD
1
Halt ramping (Ramp Function Generator output held).
0
Normal operation.
13
RAMP_IN_ZERO
1
Force Ramp Function Generator input to zero.
0
Normal operation.
14
REQ_LOCAL_LO
CK
1
Drive does not switch to local control mode (see
parameter
0
Drive can switch between local and external control
modes.
16
FB_LOCAL_CTL
1
Local mode for control from the fieldbus is requested.
Steal control from the active source.
0
(no op)
17
FB_LOCAL_REF
1
Local mode for reference from the fieldbus is requested.
Steal reference from the active source.
0
(no op)
18
Reserved for
RUN_DISABLE_1
Not yet implemented.
19
Reserved
20
Reserved
Bit
Name
Value
State/Description
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...