34 Default configuration
Water default
This is the default configuration of control connections for water and waste water applications.
Default control connections for the Water default
max.
500 ohm
1…10 kohm
X1
Reference voltage and analog inputs and outputs
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency/speed reference
: 0…10 V
3
AGND
Analog input circuit common
4
+10V
Reference voltage 10 V DC
5
AI2
Actual feedback:
0…10 V
6
AGND
Analog input circuit common
7
AO1
Output frequency:
0…10 V
8
AO2
Motor current:
0…20 mA
9
AGND
Analog output circuit common
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage 24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1)
14
DI2
Not configured
15
DI3
Constant frequency/speed selection
16
DI4
Not configured
17
DI5
Not configured
18
DI6
Not configured
X6, X7, X8
Relay outputs
19
RO1C
Ready run
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault (-1)
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
Embedded fieldbus
29
B+
Embedded fieldbus, EFB (EIA-485)
30
A-
31
DGND
S4
TERM
Termination switch
S5
BIAS
Bias resistors switch
X4
Safe torque off
34
OUT1
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start. See chapter
The Safe torque off function
in the
Hardware
manual
of the drive
35
OUT2
36
SGND
37
IN1
38
IN2
X10
24 V AC/DC
40
24 V AC/DC+ in R6…R11 only: Ext. 24V AC/DC input to power up the
control unit when the main supply is disconnected.
41
24 V AC/DC- in
4)
3)
See the notes on
the next page.
4)
4)
5)
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...