Parameters 223
Defines a deadband around the setpoint. Whenever process
feedback enters the deadband, a delay timer starts. If the
feedback remains within the deadband longer than the delay
(
), the PID controller output is
frozen. Normal operation resumes after the feedback value
leaves the deadband.
0.0
0……200000.0
Deadband range.
1 = 1
Delay for the deadband. See parameter
0.0 s
0.0 … 3600.0 s
Delay for deadband area.
1 = 1 s
Defines the start limit for the sleep function. If the value is 0.0,
set 1 sleep mode is disabled.
The sleep function compares PID output (parameter
) to the value of this parameter. If
PID output remains below this value longer than the sleep
delay defined by
, the drive enters the
sleep mode and stops the motor.
0.0
0.0…200000.0
Sleep start level.
1 = 1
Defines a delay before the sleep function actually becomes
enabled, to prevent nuisance sleeping.
The delay timer starts when the sleep mode is enabled by
parameter
, and resets when the sleep
mode is disabled.
60.0 s
0.0…3600.0 s
Sleep start delay.
1 = 1 s
Defines a boost time for the sleep boost step. See parameter
.
0.0 s
0.0…3600.0 s
Sleep boost time.
1 = 1 s
When the drive is entering sleep mode, the process setpoint
is increased by this value for the time defined by parameter
.
If active, sleep boost is aborted when the drive wakes up.
0.0 PID
customer
units
0.0…200000.0 PID
customer units
Sleep boost step.
1 = 1 PID
customer unit
No.
Name/Value
Description
Def/FbEq16
Setpoint
Time
Feedback
PID controller
output
PID controller
output frozen
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...