Parameters 215
Selects the second source of process feedback. The second
source is used only if the setpoint function requires two
inputs.
For the selections, see parameter
Defines how process feedback is calculated from the two
feedback sources selected by parameters
.
The result of the function (for any selection) is multiplied by
parameter
. (That is why in
selections 12 and 13, the multiplier k is constant 1.)
In1
Source 1.
0
In1+In2
Sum of sources 1 and 2.
1
In1-In2
Source 2 subtracted from source 1.
2
In1*In2
Source 1 multiplied by source 2.
3
In1/In2
Source 1 divided by source 2.
4
MIN(In1,In2)
Smaller of the two sources.
5
MAX(In1,In2)
Greater of the two sources.
6
AVE(In1,In2)
Average of the two sources.
7
sqrt(In1)
Square root of source 1.
8
sqrt(In1-In2)
Square root of (source 1 - source 2).
9
sqrt(In1+In2)
Square root of (source 1 + source 2).
10
sqrt(In1)+sqrt(In2)
Square root of source 1 + square root of source 2.
11
k*sqrt(In1)
Square root of source 1. (k = 1)
12
k*sqrt(In1-In2)
Square root of (source 1 - source 2). (k = 1)
13
Defines the filter time constant for process feedback.
0.000 s
0.000…30.000 s
Feedback filter time.
1 = 1 s
Defines, together with parameter
,
a general scaling factor for the process PID control chain.
If the parameter is set to zero, automatic setpoint scaling is
activated, where suitable setpoint scale is calculated
according to selected setpoint source. Actual setpoint scale is
shown in parameter
.
The scaling can be utilized when, for example, the process
setpoint is input in Hz, and the output of the PID controller is
used as an rpm value in speed control. In this case, this
parameter might be set to 50, and parameter
to the
nominal motor speed at 50 Hz.
In effect, the output of the PID controller = [
] when
deviation (setpoint - feedback) = [
] and [
] = 1.
Note:
The scaling is based on the ratio between
and
. For example, the values 50 and 1500 would produce
the same scaling as 1 and 30.
0.00
-200000.00…
200000.00
Scaling.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...