160 Parameters
Defines the low limit for critical speed range 2.
Note:
This value must be less than or equal to the value of
0.00 rpm
-30000.00…
30000.00 rpm
Low limit for critical speed 2.
See par.
Defines the high limit for critical speed range 2.
Note:
This value must be greater than or equal to the value of
.
0.00 rpm
-30000.00…
30000.00 rpm
High limit for critical speed 2.
See par.
Defines the low limit for critical speed range 3.
Note:
This value must be less than or equal to the value of
0.00 rpm
-30000.00…
30000.00 rpm
Low limit for critical speed 3.
See par.
Defines the high limit for critical speed range 3.
Note:
This value must be greater than or equal to the value of
.
0.00 rpm
-30000.00…
30000.00 rpm
High limit for critical speed 3.
See par.
Activates and selects the mode of the motor potentiometer.
See section
(page
Disabled
Motor potentiometer is disabled and its value set to 0.
0
Enabled (init at stop
/power-up)
When enabled, the motor potentiometer first adopts the value
defined by parameter
Motor potentiometer initial value
.
The value can then be adjusted from the up and down
sources defined by parameters
Motor potentiometer down source
A stop or a power cycle will reset the motor potentiometer to
the initial value (
).
1
Enabled (resume
always)
As
Enabled (init at stop /power-up)
, but the motor
potentiometer value is retained over a power cycle.
2
Enabled (init to
actual)
Whenever another reference source is selected, the value of
the motor potentiometer follows that reference. After the
source of reference returns to the motor potentiometer, its
value can again be changed by the up and down sources
(defined by
and
).
3
Motor
potentiometer initial
value
Defines an initial value (starting point) for the motor
potentiometer. See the selections of parameter
.
0.00
-32768.00…
32767.00
Initial value for motor potentiometer.
1 = 1
Selects the source of motor potentiometer up signal.
0 = No change
1 = Increase motor potentiometer value. (If both the up and
down sources are on, the potentiometer value will not
change.)
Not selected
0.
0
Selected
1.
1
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...