Parameters 295
Selects the type of the motor identification routine (ID run)
performed at the next start of the drive. During the ID run, the
drive will identify the characteristics of the motor for optimum
motor control.
If no ID run has been performed yet (or if default parameter
values have been restored using parameter
), this parameter is automatically set to
signifying that an ID run must be performed.
After the ID run, the drive stops and this parameter is
automatically set to
.
Notes:
• To ensure that the ID run can work properly, the drive limits
in group
(maximum speed and minimum speed, and
maximum torque and minimum torque) must to be large
enough (the range specified by the limits must be wide
enough. If eg. speed limits are less than the motor nominal
speed, the ID run cannot be completed.
• For
ID run, the machinery must always be
de-coupled from the motor.
• With a permanent magnet or synchronous reluctance
motor, a
or
ID run requires that
the motor shaft is NOT locked and the load torque is less
than 10%.
• With scalar control mode (
=
), the ID run is not requested automatically.
However, an ID run can be performed for more accurate
torque estimation.
• Once the ID run is activated, it can be canceled by
stopping the drive.
• The ID run must be performed every time any of the motor
parameters (
) have been changed.
• Ensure that the Safe Torque Off and emergency stop
circuits (if any) are closed during the ID run.
• Mechanical brake (if present) is not opened by the logic for
the ID run.
• This parameter cannot be changed while the drive is
running.
None
No motor ID run is requested. This mode can be selected
only if the ID run (
) has
already been performed once.
0
Normal
Normal ID run. Guarantees good control accuracy for all
cases. The ID run takes about 90 seconds. This mode should
be selected whenever it is possible.
Notes:
• If the load torque will be higher than 20% of motor nominal
torque, or if the machinery is not able to withstand the
nominal torque transient during the ID run, then the driven
machinery must be de-coupled from the motor during a
Normal ID run.
• Check the direction of rotation of the motor before starting
the ID run. During the run, the motor will rotate in the
forward direction.
WARNING!
The motor will run at up to approximately
50…100% of the nominal speed during the ID run.
ENSURE THAT IT IS SAFE TO RUN THE MOTOR
BEFORE PERFORMING THE ID RUN!
1
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...