354 Fault tracing
0002 Auxiliary fan 2 broken.
5090
STO hardware failure
STO hardware diagnostics has
detected hardware failure.
Contact your local ABB
representative for hardware
replacement.
5091
Safe torque off
Programmable fault:
Safe torque off function is
active, ie. safety circuit
signal(s) connected to
connector STO is broken
during start or run.
Check safety circuit connections. For
more information, see chapter
The
Safe torque off function
in the
Hardware manual
of the drive and
description of parameter
.
5092
PU logic error
Power unit memory has
cleared.
Contact your local ABB
representative.
5093
Rating ID mismatch
The hardware of the drive does
not match the information
stored in the memory. This
may occur eg. after a firmware
update.
Cycle the power to the drive. You may
have to be repeat this.
5094
Measurement circuit
temperature
Problem with internal
temperature measurement of
the drive.
Contact your local ABB
representative.
5098
I/O communication
loss
Internal standard I/O
communication failure.
Try resetting the fault or reboot the
drive.
50A0
Fan
Cooling fan stuck or
disconnected.
Check fan operation and connection.
Replace fan if faulty.
5682
Power unit lost
Connection between the drive
control unit and the power unit
is lost.
Check the connection between the
control unit and the power unit.
5691
Measurement circuit
ADC
Measurement circuit fault.
Contact your local ABB
representative.
5692
PU board powerfail
Power unit power supply
failure.
Contact your local ABB
representative.
5693
Measurement circuit
DFF
Measurement circuit fault.
Contact your local ABB
representative.
5696
PU state feedback
State feedback from output
phases does not match control
signals.
Contact your local ABB
representative.
5697
Charging feedback
Charging feedback signal
missing.
Check the feedback signal coming
from the charging system
5698
Unknown PU fault
The power unit logic has
generated a fault which is not
known by the software.
Check the logic and software
compatibility.
6181
FPGA version
incompatible
Firmware and FPGA versions
are incompatible.
Reboot the control unit (using
parameter
)
or by cycling power. If the problem
persists, contact your local ABB
representative
6306
FBA A mapping file
Fieldbus adapter A mapping
file read error.
Contact your local ABB
representative.
Code
(hex)
Fault / Aux. code
Cause
What to do
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...