134 Parameters
CMOD-01
CMOD-01 multifunction extension module (external
24 V AC/DC and digital I/O).
1
CMOD-02
CMOD-02 multifunction extension module (external
24 V AC/DC and isolated PTC interface).
2
CHDI-01
CHDI-01 115/230 V digital input extension module.
3
CPTC-02
4
Displays the status of the digital inputs DI7…DI12 on the
extension module
Bit 0 indicates the status of DI7.
Example:
001001b = DI7 and DI10 are on, remainder are off.
This parameter is read-only.
-
0000h…FFFFh
Status of digital input/outputs.
1 = 1
Displays the status of the relay outputs RO4 and RO5 and
digital output DO1 on the extension module.
Bits 0…1 indicates the status of RO4…RO5; bit 5 indicates
the status of DO1.
Example:
100101b = RO4 is on, RO5 is off. and DO1 is on.
This parameter is read-only.
-
0000h…FFFFh
Status of relay/digital outputs.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
DI7
1 = Digital input 7 is ON.
1
DI8
1 = Digital input 8 is ON.
2
DI9
1 = Digital input 9 is ON.
3
DI10
1 = Digital input 10 is ON.
4
DI11
1 = Digital input 11 is ON.
5
DI12
1 = Digital input 12 is ON.
6…15
Reserved
Bit
Name
Description
0
RO4
1 = Relay output 4 is ON.
1
RO5
1 = Relay output 5 is ON
2…4
Reserved
5
DO1
1 = Digital output 1 is ON.
6…15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...