360 Fault tracing
0003 Maximum torque limit too low.
Check settings of parameter
, and the torque
limits in group
.
Make sure that the maximum torque
limit in force is greater than 100%.
0004 Current measurement
calibration did not finish within
reasonable time
Contact your local ABB
representative.
0005…0008 Internal error.
Contact your local ABB
representative.
0009 (Asynchronous motors only)
Acceleration did not finish
within reasonable time.
Contact your local ABB
representative.
000A (Asynchronous motors only)
Deceleration did not finish
within reasonable time.
Contact your local ABB
representative.
000B (Asynchronous motors only)
Speed dropped to zero during
ID run.
Contact your local ABB
representative.
000C (Permanent magnet motors
only)
First acceleration did not finish
within reasonable time.
Contact your local ABB
representative.
000D (Permanent magnet motors
only)
Second acceleration did not
finish within reasonable time.
Contact your local ABB
representative.
000E…0010 Internal error.
Contact your local ABB
representative.
0011 (Synchronous reluctance
motors only)
Pulse test error.
Contact your local ABB
representative.
0012 Motor too large for advanced
standstill ID run.
Check that the motor and drive sizes
are compatible.
Contact your local ABB
representative.
0013 (Asynchronous motors only)
Motor data error.
Check that the motor nominal value
settings in the drive are the same as
in the motor nameplate.
Contact your local ABB
representative.
FF63
STO diagnostics
failure.
SW internal malfunction.
Reboot the control unit (using
parameter
)
or by cycling power.
FF81
FB A force trip
A fault trip command has been
received through fieldbus
adapter A.
Check the fault information provided
by the PLC.
FF8E
EFB force trip
A fault trip command has been
received through the
embedded fieldbus interface.
Check the fault information provided
by the PLC.
Code
(hex)
Fault / Aux. code
Cause
What to do
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...