Parameters 293
Selects the motor control mode.
Vector
Vector control. Vector control has better accuracy than scalar
control but cannot be used in all situations (see selection
below).
Requires motor identification run (ID run). See parameter
Note:
In vector control the drive performs a standstill ID run at
the first start if ID run has not been previously performed. A
new start command is required after standstill ID run.
Note:
To achieve a better motor control performance, you can
perform a normal ID run without load.
See also section
(page
0
Scalar
Scalar control. Suitable for most applications, if top
performance is not required.
Motor identification run is not required.
Note:
Scalar control must be used in the following situations:
• with multimotor systems 1) if the load is not equally shared
between the motors, 2) if the motors are of different sizes,
or 3) if the motors are going to be changed after the motor
identification (ID run)
• if the nominal current of the motor is less than 1/6 of the
nominal output current of the drive
• if the drive is used with no motor connected (for example,
for test purposes).
Note:
Correct motor operation requires that the magnetizing
current of the motor does not exceed 90% of the nominal
current of the inverter.
See also section
(page
), and section
1
Defines the nominal motor current. Must be equal to the value
on the motor rating plate. If multiple motors are connected to
the drive, enter the total current of the motors.
Notes:
• Correct motor operation requires that the magnetizing
current of the motor does not exceed 90% of the nominal
current of the drive.
• This parameter cannot be changed while the drive is
running.
0.0 A
0.0…6400.0 A
Nominal current of the motor. The allowable range is 1/6…2 ×
I
N
of the drive (0…2 ×
I
N
with scalar control mode).
1 = 1 A
Defines the nominal motor voltage supplied to the motor. This
setting must match the value on the rating plate of the motor.
Notes:
• With permanent magnet motors, the nominal voltage is the
BackEMF voltage at nominal speed of the motor. If the
voltage is given as voltage per rpm, e.g. 60 V per
1000 rpm, the voltage for a nominal speed of 3000 rpm is
3 × 60 V = 180 V.
• The stress on the motor insulation is always dependent on
the drive supply voltage. This also applies to the case
where the motor voltage rating is lower than that of the
drive and the supply.
• This parameter cannot be changed while the drive is
running.
0.0 V
0.0…960.0 V
Nominal voltage of the motor.
10 = 1 V
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...