Parameters 169
Control panel (ref
copied)
Panel reference (
, see page
) for
the previous control location is used as the reference when
the control location changes if the references for the two
locations are of the same type (eg
frequency/speed/torque/PID); otherwise, the actual signal is
used as the new reference.
19
Level control
Parameter
(output of the Level control
function).
30
). -
Determines how constant frequencies are selected, and
whether the rotation direction signal is considered or not
when applying a constant frequency.
0001b
0000b…0011b
Constant frequency configuration word.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Ext1 -> Ext2
Ext1 reference
Ext2 reference
Active reference
t
Inactive reference
Reference
Bit
Name
Information
0
Const freq
mode
1 = Packed: 7 constant frequencies are selectable using the three
sources defined by parameters
and
.
0 = Separate: Constant frequencies 1, 2 and 3 are separately activated
by the sources defined by parameters
,
respectively. In case of conflict, the constant frequency with the smaller
number takes priority.
1
Direction
enable
1 = Start dir: To determine running direction for a constant speed, the
sign of the constant speed setting (parameters
…
) is
multiplied by the direction signal (forward: +1, reverse: -1). This
effectively allows the drive to have 14 (7 forward, 7 reverse) constant
speeds if all values in
…
are positive.
WARNING:
If the direction signal is reverse and the active
constant speed is negative, the drive will run in the forward
direction.
0 = Accord Par: The running direction for the constant speed is
determined by the sign of the constant speed setting (parameters
).
2…15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...