256 Parameters
76
Multipump configuration parameters.
See sections
Intelligent pump control (IPC)
(page
),
(page
) and
Note:
Parameters are dynamically hidden based on selection
of pumping mode (
) and
number of motors (
).
Displays the running/stopped status of the PFC motors.
PFC1, PFC2, PFC3, PFC4, PFC5 and PFC6 always
correspond to the 1st…46th motor of the PFC system. If
auxiliary PFC is set to
, PFC1 represents the motor connected to the
drive and PFC2 the first auxiliary motor (the 2nd motor of the
system). If
is set to
, PFC1 is the first motor,
PFC2 the 2nd. The drive can be connected to any of these
motors depending on the Autochange functionality.
-
0000h…FFFFh
Status of the PFC relay outputs.
1 = 1
Displays the status of multipump system in text from.
This parameter provides a quick system overview, e.g. if the
parameter is added to the Home view on the control panel.
PFC disabled
Displays the measured level.
This parameter is active when parameter
.
0.00...32767.00 m
Measured level in meters.
1 = 1 m
Displays the measured level as a percentage of level control
operation area.
The signal is scaled to stop level 1 and full speed level.
0...100 %
Measured level in %.
1 = 1 %
Displays the level control speed reference.
-2147483648...
2147483648 rpm
Level control speed reference.
1 = 1 rpm
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Value
0
PFC 1 running
0 = Stop, 1 = Start
1
PFC 2 running
0 = Stop, 1 = Start
2
PFC 3 running
0 = Stop, 1 = Start
3
PFC 4 running
0 = Stop, 1 = Start
4
PFC 5 running
0 = Stop, 1 = Start
5
PFC 6 running
0 = Stop, 1 = Start
6…15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...