Parameters 193
Defines when timer 1 is active.
0111 1000
0000b
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Monday
1 = Monday is an active start day.
1
Tuesday
1 = Tuesday is an active start day.
2
Wednesday
1 = Wednesday is an active start day.
3
Thursday
1 = Thursday is an active start day.
4
Friday
1 = Friday is an active start day.
5
Saturday
1 = Saturday is an active start day.
6
Sunday
1 = Sunday is an active start day.
7
Season 1
1 = Timer is active in season 1.
8
Season 2
1 = Timer is active in season 2.
9
Season 3
1 = Timer is active in season 3.
10
Season 4
1 = Timer is active in season 4.
11
Exceptions
0 = Exceptions days are disabled. The timer follows only
weekday and season settings (bits 0…10 in the timer
configuration) and the start time and duration of the timer
(see
and
).
Exception day settings, parameters
…
, do not
have any effect on this timer.
1 = Exception days are enabled. The timer is active during
the weekdays and seasons defined with bits 0…10 and the
times defined by
In addition, the timer is active during the exception days
defined with bit 12, bit 13 and parameters
. If bit
12 and bit 13 are both zero, the timer is inactive during the
exception days.
12
Holidays
This bit has no effect unless bit 11 = 1 (Exceptions days are
enabled).
When bits 11 and 12 are both 1, the timer is active during the
weekdays and seasons defined with bits 0…10 and times
defined by parameters
.
In addition, the timer is active when the ongoing day is
defined as Exception day Holiday by parameters
and the current time matches with the time
. During Exception days,
weekday and season bits are ignored.
13
Workdays
This bit has no effect unless bit 11 = 1 (Exceptions enabled).
When bits 11 and 13 are both 1, the Timer is active during the
weekdays and seasons defined with bits 0…10 and the times
defined by parameters
.
In addition, the timer is active when the ongoing day is
defined as Exception day Workday by parameters
and the current time matches with the time
. During Exception days,
weekday and season bits are ignored.
14…15 Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...