246 Parameters
Displays the application program revision of the adapter
module in format axyz, where a = major revision number, xy =
minor revision number, z = correction number or letter.
Example: 190A = revision 1.90A.
Application program version of adapter module.
-
52
Selection of data to be transferred from drive to fieldbus
controller through fieldbus adapter A.
Note:
32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
select data to be transferred from
the drive to the fieldbus controller through fieldbus adapter A.
None
None.
0
CW 16bit
Control Word (16 bits)
1
Ref1 16bit
Reference REF1 (16 bits)
2
Ref2 16bit
Reference REF2 (16 bits)
3
SW 16bit
Status Word (16 bits)
4
Act1 16bit
Actual value ACT1 (16 bits)
5
Act2 16bit
Actual value ACT2 (16 bits)
6
Reserved
7…10
CW 32bit
Control Word (32 bits)
11
Ref1 32bit
Reference REF1 (32 bits)
12
Ref2 32bit
Reference REF2 (32 bits)
13
SW 32bit
Status Word (32 bits)
14
Act1 32bit
Actual value ACT1 (32 bits)
15
Act2 32bit
Actual value ACT2 (32 bits)
16
Reserved
17…23
SW2 16bit
Status Word 2 (16 bits)
24
Source selection (see
). -
…
…
…
…
See parameter
.
53
Selection of data to be transferred from fieldbus controller to
drive through fieldbus adapter A.
Note:
32-bit values require two consecutive parameters.
Whenever a 32-bit value is selected in a data parameter, the
next parameter is automatically reserved.
Parameters
select data to be transferred from
the fieldbus controller to the drive through fieldbus adapter A.
None
None.
0
CW 16bit
Control Word (16 bits)
1
Ref1 16bit
Reference REF1 (16 bits)
2
Ref2 16bit
Reference REF2 (16 bits)
3
Reserved
7…10
CW 32bit
Control Word (32 bits)
11
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...