124 Parameters
12
Configuration of standard analog inputs.
The true readings of the analog inputs can be overridden for
eg. testing purposes. A forced value parameter is provided for
each analog input, and its value is applied whenever the
corresponding bit in this parameter is 1.
Note:
and
) have no effect on forced AI values
(parameters
Note:
Boot and power cycle reset the force selections
(parameters
and
0000h
0000h…FFFFh
Forced values selector for analog inputs AI1 and AI2.
1 = 1
Selects how the drive reacts when an analog input signal
moves out of the minimum and/or maximum limits specified
for the input.
The inputs and the limits to be observed are selected by
parameter
No action
No action taken.
0
Fault
Drive trips on
.
1
Warning
Drive generates an
warning.
2
Last speed
Drive generates a warning (
) and freezes
the speed (or frequency) to the level the drive was operating
at. The speed/frequency is determined on the basis of actual
speed using 850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
3
Speed ref safe
Drive generates a warning (
) and sets the
speed to the speed defined by parameter
(or
when frequency reference
is being used).
WARNING!
Make sure that it is safe to continue
operation in case of a communication break.
4
Specifies the analog input limits to be supervised. See
parameter
0000h
0000h…FFFFh
Activation of analog input supervision.
1 = 1
No.
Name/Value
Description
Def/FbEq16
Bit
Value
0
1 = Force AI1 to value of parameter
1
1 = Force AI2 to value of parameter
2…15
Reserved
Bit
Name
Description
0
AI1 < MIN
1 = Minimum limit supervision of AI1 active.
1
AI1 > MAX
1 = Maximum limit supervision of AI1 active.
2
AI2 < MIN
1 = Minimum limit supervision of AI2 active.
3
AI2 > MAX
1 = Maximum limit supervision of AI2 active.
4…15
Reserved
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...