Fault tracing 357
6882
Text 32-bit table
overflow
Internal fault.
Reset the fault. Contact your local
ABB representative if the fault
persists.
6885
Text file overflow
Internal fault.
Reset the fault. Contact your local
ABB representative if the fault
persists.
7081
Control panel loss
Programmable fault:
Control panel or PC tool
selected as active control
location for drive has ceased
communicating.
Check PC tool or control panel
connection.
Check control panel connector.
Disconnect and reconnect the control
panel.
7085
Incompatible option
module
Fieldbus option module not
supported.
Replace the module with a supported
type.
7100
Excitation current
Excitation current feedback low
or missing
7121
Motor stall
Programmable fault:
Motor is operating in stall
region because of e.g.
excessive load or insufficient
motor power.
Check motor load and drive ratings.
Check fault function parameters.
7310
Overspeed
Motor is turning faster than
highest allowed speed due to
incorrectly set
minimum/maximum speed,
insufficient braking torque or
changes in load when using
torque reference.
Check minimum/maximum speed
settings, parameters
Check adequacy of motor braking
torque.
Check applicability of torque control.
73F0
Overfrequency
Maximum allowed output
frequency exceeded.
Contact your local ABB
representative.
73B0
Emergency ramp
failed
Emergency stop did not finish
within expected time.
Check the settings of parameters
and
Check the predefined ramp times
(
…
for mode Off1,
for mode Off3).
7510
FBA A communication
Programmable fault:
Cyclical communication
between drive and fieldbus
adapter module A or between
PLC and fieldbus adapter
module A is lost.
Check status of fieldbus
communication. See user
documentation of fieldbus interface.
Check settings of parameter groups
.
Check cable connections.
Check if communication master is
able to communicate.
8001
ULC underload fault
User load curve: Signal has
been too long under the
underload curve.
See parameter
8002
ULC overload fault
User load curve: Signal has
been too long over the
overload curve.
See parameter
Code
(hex)
Fault / Aux. code
Cause
What to do
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...