Parameters 175
Displays the torque controller limitation status word.
This parameter is read-only.
-
0000h…FFFFh
Torque limitation status word.
1 = 1
Defines the minimum allowed speed.
WARNING!
This value must not be higher than
.
WARNING!
In speed control mode only. In frequency
control mode, use frequency limits (
).
0.00 rpm
-30000.00…
30000.00 rpm
Minimum allowed speed.
See par.
Defines the maximum allowed speed.
Note:
This parameter does not affect the speed acceleration
and deceleration ramp times. See parameter
WARNING!
This value must not be lower than
.
WARNING!
In speed control mode only. In frequency
control mode, use frequency limits (
).
1500.00 rpm;
1800.00 rpm
(
b0)
-30000.00…
30000.00 rpm
Maximum speed.
See par.
No.
Name/Value
Description
Def/FbEq16
Bit
Name
Description
0
Undervoltage
*1 = Intermediate DC circuit undervoltage
1
Overvoltage
*1 = Intermediate DC circuit overvoltage
2
Minimum torque *1 = Torque is being limited by
3
Maximum torque *1 = Torque is being limited by
4
Internal current
1 = An inverter current limit (identified by bits 8…11) is active
5
Load angle
(With permanent magnet motors and reluctance motors only)
1 = Load angle limit is active, ie. the motor cannot produce any more
torque
6
Motor pullout
(With asynchronous motors only)
Motor pull-out limit is active, ie. the motor cannot produce any more
torque
7
Reserved
8
Thermal
1 = Input current is being limited by the main circuit thermal limit
9
Max current
*1 = Maximum output current (
I
MAX
) is being limited
10
User current
*1 = Output current is being limited by
11
Thermal IGBT
*1 = Output current is being limited by a calculated thermal current
value
12…15 Reserved
*Only one out of bits 0…3, and one out of bits 9…11 can be on simultaneously. The bit typically
indicates the limit that is exceeded first.
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...