Parameters 203
Defines the fault limit for temperature supervision function 2.
When measured temperature 1 exceeds the limit, the drive
trips on fault
The unit is selected by parameter
.
Note:
With a PTC sensor, changing the value of this
parameter has no effect on fault generation. When PTC is
over the triggering threshold of the CMOD-02 (see the
Hardware manual
), the drive trips on the fault and when PTC
has decreased below recovery threshold of the CMOD-02
(see the
Hardware manual
), the fault is reset.
130 °C or
266 °F
-60…5000 °C or
-76…9032 °F
Fault limit for temperature monitoring function 2.
1 = 1 °
Defines the warning limit for temperature supervision
function 2. When measured temperature 1 exceeds the limit,
warning
is generated.
The unit is selected by parameter
.
Note:
With a PTC sensor, changing the value of this
parameter has no effect on warning generation. When PTC is
over the triggering threshold of the CMOD-02 (see the
Hardware manual
), the drive trips on the fault and when PTC
has decreased below recovery threshold of the CMOD-02
(see the
Hardware manual
), the fault is reset.
110 °C or
230 °F
-60…5000 °C or
-76…9032 °F
Warning limit for temperature monitoring function 2.
1 = 1 °
Specifies the analog input when the setting of
requires measurement through an
analog input.
Not selected
None.
0
AI1 actual value
Analog input AI1 on the control unit.
1
AI2 actual value
Analog input AI2 on the control unit.
2
). -
Enables safe motor temperature.
Off
Safe motor temperature is off.
On
Safe motor temperature is on.
Defines the ambient temperature of the motor for the motor
thermal protection model. The unit is selected by parameter
.
The motor thermal protection model estimates the motor
temperature on the basis of parameters
…
. The
motor temperature increases if it operates in the region above
the load curve, and decreases if it operates in the region
below the load curve.
WARNING!
The model cannot protect the motor if the
motor does not cool properly because of dust, dirt, etc.
20 °C or
68 °F
-60…100 °C or
-76 … 212 °F
Ambient temperature.
1 = 1°
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...