Fault tracing 341
A2B4
Short circuit
Short-circuit in motor cable(s)
or motor.
Check motor and motor cable for
cabling errors.
Check motor and motor cable
(including phasing and delta/star
connection).
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable. See chapter
Electrical
installation
, section
Checking the
insulation of the assembly
in the
Hardware manual
of the drive.
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
A2BA
IGBT overload
Excessive IGBT junction to
case temperature. This
warning protects the IGBT(s)
and can be activated by a short
circuit in the motor cable.
Check motor cable.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive
power.
A3A1
DC link overvoltage
Intermediate circuit DC voltage
too high (when the drive is
stopped).
Check the supply voltage setting
(parameter
). Note
that the wrong setting of the parameter
may cause the motor to rush
uncontrollably, or may overload the
resistor.
Check the supply voltage.
If the problem persists, contact your
local ABB representative.
A3A2
DC link undervoltage
Intermediate circuit DC voltage
too low (when the drive is
stopped).
A3AA
DC not charged
The voltage of the intermediate
DC circuit has not yet risen to
operating level.
A490
Incorrect temperature
sensor setup
Temperature cannot be
supervised due to incorrect
adapter setup.
Check the settings of temperature
source parameters
A491
External temperature
1
(Editable message text)
Measured temperature 1 has
exceeded warning limit.
Check the value of parameter
.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of
.
A492
External temperature
2
(Editable message text)
Measured temperature 2 has
exceeded warning limit.
Check the value of parameter
.
Check the cooling of the motor (or other
equipment whose temperature is being
measured).
Check the value of
.
A4A0
Control board
temperature
Control board temperature is
too high.
Check the auxiliary code. See actions
for each code below.
(none) Temperature above warning
limit
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
1 Thermistor broken
Contact an ABB service representative
for control board replacement.
Code
(hex)
Warning / Aux. code
Cause
What to do
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...