292 Parameters
Defines the permanent magnet flux.
Note:
This parameter is valid only for permanent magnet
motors.
0.00000 p.u.
0.00000… 2.00000
p.u
Permanent magnet flux in per unit.
-
Defines the stator resistance
R
S
of the motor model.
0.00000 ohm
0.00000…100.0000
0 ohm
Stator resistance.
-
Defines the rotor resistance
R
R
of the motor model.
Note:
This parameter is valid only for asynchronous motors.
0.00000 ohm
0.00000…100.0000
0 ohm
Rotor resistance.
-
Defines the main inductance
L
M
of the motor model.
Note:
This parameter is valid only for asynchronous motors.
0.00 mH
0.00…100000.00
mH
Main inductance.
1 = 10000
mH
Defines the leakage inductance
σ
L
S
.
Note:
This parameter is valid only for asynchronous motors.
0.00 mH
0.00…100000.00
mH
Leakage inductance.
1 = 10000
mH
Defines the direct axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 mH
0.00…100000.00
mH
Direct axis inductance.
1 = 10000
mH
Defines the quadrature axis (synchronous) inductance.
Note:
This parameter is valid only for permanent magnet
motors.
0.00 mH
0.00…100000.00
mH
Quadrature axis inductance.
1 = 10000
mH
99
Motor configuration settings.
Selects the motor type.
Note:
This parameter cannot be changed while the drive is
running.
Asynchronous
motor
Standard squirrel cage AC induction motor (asynchronous
induction motor).
0
Permanent magnet
motor
Permanent magnet motor. Three-phase AC synchronous
motor with permanent magnet rotor and sinusoidal BackEMF
voltage.
Note:
With permanent magnet motors special attention must
be paid on setting the motor nominal values correctly in
parameter group
. You must use vector control.
If the nominal BackEMF voltage of the motor is not available,
a full ID run should be performed for improving performance.
1
SynRM
Synchronous reluctance motor. Three-phase AC
synchronous motor with salient pole rotor without permanent
magnets. You must use vector control.
2
No.
Name/Value
Description
Def/FbEq16
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...