Status word allocation for
Status3
parameter
You can find a description for each parameter in section I/Os of SitrLRPA (Page 654).
Status bit
Parameter
0
Not used
8
PV2AH_Act.Value
9
PV2WH_Act.Value
10
PV2WL_Act.Value
11
PV2AL_Act.Value
12
PV2AH_En
13
PV2WH_En
14 - 15
Not used
16
PV2WL_En
17
PV2AL_En
18
PV2AH_MsgEn
19
PV2WH_MsgEn
20 - 21
Not used
22
PV2WL_MsgEn
23
PV2AL_MsgEn
24
QWronDev
25
1 = error when reading acyclic data (active only for the duration of one cycle)
26
1 = error when writing acyclic data (active only for the duration of one cycle)
27
Analog input 2 (PV2) configured
28
Show value for fill time
29
Show value for empty time
30
Fill time and empty time visible
31
1 = display "Write configuration data" in the faceplate
14.1.2
Operating modes of SitrLRPA
The block can be operated using the following modes:
● On
● Out of service
"On"
You can find general information about the "On" mode in the On chapter.
"Out of service"
You can find general information about the "Out of service" mode in the Out of service section.
The descriptions of the operating modes are identical for the SitrLRPA and the APL; refer to the
Online Help for the standard APL blocks for information on them.
SITRANS LR PA
14.1 SitrLRPA
SITRANS Library for PCS 7
644
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...