Parameter
Description
Type
Default
SimTot3Li
Totalizer 3 value used for
SimOnLi.Value
=
1 (
SimLiOp.Value
= 1)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
SimDQuant
Dosing quantity used for
SimOnLi.Value
= 1
(
SimLiOp.Value
= 1)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
InPassword
Password of FC430 PA
DWORD
16#FFFFFFFF
InPV2PreVal
PV2 - Preset Value
REAL
0.0
InPV3PreVal
PV3 - Preset Value
REAL
0.0
InPV4PreVal
PV4 - Preset Value
REAL
0.0
InPV1_Hyst*
(analog
PV2,PV3,PV4
)
Limiter
PV1
:
Hysteresis for alarm and warning limits
REAL
0.0
InPV1_AH_Li
m*
(analog
PV2,PV3,PV4
)
Limiter
PV1
:
Alarm limit (high)
REAL
0.0
InPV1_WH_Li
m*
(analog
PV2,PV3,PV4
)
Limiter
PV1
:
Warning limit (high)
REAL
0.0
InPV1_WL_Li
m*
(analog
PV2,PV3,PV4
)
Limiter
PV1
:
Limit warning (low)
REAL
0.0
InPV1_AL_Li
m*
(analog
PV2,PV3,PV4
)
Limiter
PV1
:
Alarm limit (low)
REAL
0.0
PV1_AH_DC*
(analog
PV2,PV3,PV4
)
Limiter
PV1
:
Delay time for incoming alarms with overrange
process value [s]
REAL
0.0
PV1_AH_DG*
(analog
PV2,PV3,PV4
)
Limiter
PV1
:
Delay time for outgoing alarms with overrange
process value [s]
REAL
0.0
PV1_WH_DC
*
(analog
PV2,PV3,PV4
)
Limiter
PV1
:
Delay time for incoming warning messages
with overrange process value [s]
REAL
0.0
SITRANS FC430 PA
13.1 SiFC43PA
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
569
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...