Parameter
Description
Type
Default
DSta
Current dosing state from MAG6000
(B_STA from HW Config):
● 16#00: Dosing disabled
● 16#01: Dosing enabled but stopped
● 16#02: Dosing enabled and active
● 16#03: dosing enabled but in pause
state
BYTE
DosEnd
1 = End of dosing
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
DOnRun
1 = dosing enabled and active (DSta
=16#02)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
DOnStp
1 = dosing enabled but stopped (DSta
=16#01)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
DOff
1 = dosing disabled (DSta =16#00)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
DOnPaused
1 = dosing enabled, but in pause state
(DSta =16#03)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
DLockAct
Dosing unit: 1 = at least one interlock (in‐
puts Permit, Interlock, or Protect) is ac‐
tive
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
GrpErr
1 = Group error pending
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
RdyToStart2
Dosing unit: 1 = Active start readiness
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
RdyToReset2
Dosing unit. 1 = ready for reset via input
Rst2Li, or by means of commands in
"automatic mode"
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
Oos1Act
Totalizer 1: 1 = Totalizer 1 "Out of serv‐
ice"
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
On1Act
Totalizer 1: 1 = Totalizer 1 not "Out of
service"
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SITRANS F M MAG 6000
5.1 Mag6T
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
105
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...