Status bit
Parameter
24
GradLEn
25
GradHUpMsgEn
26
GradHDnMsgEn
27
GradLMsgEn
28
0 = decreasing measured value
1 = increasing measured value
29
BypassAct.Value
30
Not used
31
MS_RelOp
Status word allocation for
Status3
parameter
Status bit
Parameter
0
Effective signal 1 of the message block interconnected via
EventTsIn
1
Effective signal 2 of the message block interconnected via
EventTsIn
2
Effective signal 3 of the message block interconnected via
EventTsIn
3
Effective signal 4 of the message block interconnected via
EventTsIn
4
Effective signal 5 of the message block interconnected via
EventTsIn
5
Effective signal 6 of the message block interconnected via
EventTsIn
6
Effective signal 7 of the message block interconnected via
EventTsIn
7
Effective signal 8 of the message block interconnected via
EventTsIn
8
Tot_AH_Act.Value
9
Tot_WH_Act.Value
10
Tot_WL_Act.Value
11
Tot_AL_Act.Value
12
Tot_AH_En
13
Tot_WH_En
14-15
Not used
16
Tot_WL_En
17
Tot_AL_En
18
Tot_AH_MsgEn
19
Tot_WH_MsgEn
20-21
Not used
22
Tot_WL_MsgEn
23
Tot_AL_MsgEn
24
QWronDev
25
1 = error when reading acyclic data (active only for the duration of one cycle)
26
1 = error when writing acyclic data (active only for the duration of one cycle)
27
Analog input (
PV
) configured
28
Totalizer (
Tot
) configured for the device which supports totalizer
29
Reset or presetting of the totalizer configured for the device which supports totalizer
SITRANS P PA
11.1 SitrP_PA
SITRANS Library for PCS 7
422
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...