Parameter
Description
Type
Default
DRstLi
Dosing unit: 1 = Reset interlock
via interconnection
STRUCT
● Value : BOOL
● ST: BYTE
-
● 1
● 16#FF
PV_Meas0..1
Measured value that is intercon‐
nected at the PV_In input:
0: Mass flow
1: Volume flow
2: Density
14: Not used
BYTE
14
PV_Meas2..4
Measured value that is intercon‐
nected at the PV/SV/TV/QV input:
0: Mass flow
1: Volume flow
2: Density
3: Process media temperature
4: Corrected Volume flow
5: Fraction A
6: Fraction B
7: Fraction A %
8: Fraction B %
11: Totalizer 1
12: Totalizer 2
13: Totalizer 3
14: Not used
15: Dosing (only PV_Meas2)
BYTE
14
RdCfgOp
1 = Read all configuration data
from FC430
BOOL
0
WrCfgOp
1 = Write all configuration data to
FC430
BOOL
0
ZeroAdjOp
1 = Start automatic zero balanc‐
ing
BOOL
0
InMflZFSupp
Low flow cut-off suppression
(mass flow)
(only for readback)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
InVflZFSupp
Low flow cut-off suppression (vol‐
ume flow)
(only for readback)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
GradHUpEn
1 = Enable gradient monitoring
(high) for positive changes
BOOL
1
GradHDnEn
1 = Enable gradient monitoring
(high) for negative changes
BOOL
1
GradLEn
1 = Enable gradient monitoring
(low)
BOOL
0
GradHUpMsgEn
1 = Enable gradient (high) mes‐
sage for positive changes
BOOL
1
GradHDnMsgEn
1 = Enable gradient (high) mes‐
sage for negative changes
BOOL
1
GradLMsgEn
1 = Enable gradient (low) mes‐
sage for negative changes
BOOL
1
SITRANS FC430
12.1 SitrFC43
SITRANS Library for PCS 7
488
Function Manual, 05/2019, A5E35351976-11