Process control error
The following control system fault messages can be output:
Message
instance
Message
identifier
Message class
Event
MsgEvId3
SIG4
AS process control message - fault
$$BlockComment$$ External
fault has occurred
SIG5
AS process control message - error
$$BlockComment$$ Error
reading a data record
SIG6
AS process control message - error
$$BlockComment$$ Error
writing a data record
Explanation:
$$BlockComment$$: Content of the instance-specific comment
You can interconnect an external fault (signal) to the input parameter
CSF
. If this signal changes
to
CSF
= 1, a process control error is triggered (
MsgEvld3
,
SIG4
).
Process messages
Message in‐
stance
Message identi‐
fier
Message class
Event
MsgEvId1
SIG1
Alarm - high
$$BlockComment$$ @4Y
%t#SitrFC43_MeasVal@ - high
alarm limit violated
SIG2
Warning - high
$$BlockComment$$ @4Y
%t#SitrFC43_MeasVal@ - high
warning limit violated
SIG3
Warning - low
$$BlockComment$$ @4Y
%t#SitrFC43_MeasVal@ - low
warning limit violated
SIG4
Alarm - low
$$BlockComment$$ @4Y
%t#SitrFC4_MeasVal@ - low alarm
limit violated
SIG5
Alarm - high
$$BlockComment$$ @5Y
%t#SitrFC43_MeasVal@ - high
alarm limit violated
SIG6
Warning - high
$$BlockComment$$ @5Y
%t#SitrFC43_MeasVal@ - high
warning limit violated
SIG7
Warning - low
$$BlockComment$$ @5Y
%t#SitrFC43_MeasVal@ - low
warning limit violated
SIG8
Alarm - low
$$BlockComment$$ @5Y
%t#SitrFC4_MeasVal@ - low alarm
limit violated
SITRANS FC430
12.1 SitrFC43
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
477
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...