Parameter
Description
Type
Default
L_AL_Act
1 = Fill level alarm (low) enabled.
You can change the response for this
parameter by setting
Feature
bit 28
(deactivate switching points)
and
Feature
bit 29 (high/low signal limit
violation) accordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
L_AIB_Act
1 = "Within band" alarm active.
You can change the response for this
parameter by setting
Feature
bit 28
(deactivate switching points)
and
Feature
bit 29 (high/low signal limit
violation) accordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
L_AOB_Act
1 = "Outside band" alarm active.
You can change the response for this
parameter by setting
Feature
bit 28
(deactivate switching points)
and
Feature
bit 29 (high/low signal limit
violation) accordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
Fr_AH_Act
1 = Flow alarm (high) enabled.
You can change the response for this
parameter by setting
Feature
bit 28
(deactivate switching points)
and
Feature
bit 29 (high/low signal limit
violation) accordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
Fr_AL_Act
1 = Flow alarm (low) enabled.
You can change the response for this
parameter by setting
Feature
bit 28
(deactivate switching points)
and
Feature
bit 29 (high/low signal limit
violation) accordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SumMsgAct
Summary message Active
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
ScaleOut
Measuring range of 4 to 20 mA signal
STRUCT
● High : REAL
● Low: REAL
-
● 0.0
● 0.0
CalOut
Calibration values of the sensor
STRUCT
● High : REAL
● Low: REAL
-
● 0.0
● 0.0
PV_InUnit
Unit of measure for process value
INT
0
LevelUnit
Unit of measure for the fill level value
INT
0
SpaceUnit
Unit of measure for the space value
INT
0
DistUnit
Unit of measure for the distance value
INT
0
VolUnit
Unit of measure for the volume value
INT
0
FlowUnit
Unit of measure for the flow value
INT
0
HeadUnit
Unit of measure for the head value
INT
0
SITRANS LUT400
6.1 Lut400
SITRANS Library for PCS 7
170
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...