Parameter
Description
Type
Default
FbkOpenOut
1 = Control valve is open
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
FbkOpngOut
Control valve opening feedback
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
GrpErr
1 = Group error pending
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
LocalAct
1 = "Local mode" enabled
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
LockAct
1 = Interlock (Intlock, Permit or
Protect) is active
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
ManAct
1 = "Manual mode" enabled
STRUCT
Value: BOOL
ST: BYTE
-
1
16#80
MonDynAuxVErr
1 = Feedback error auxiliary valve
due to output change
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MonDynErr
1 = Feedback error control valve
due to control change
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MonStaAuxVErr
1 = Feedback error from auxiliary
valve due to unexpected feedback
change
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MonStaErr
1 = Feedback error from control
valve due to unexpected feedback
change
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MS_Release
Release for maintenance:
1 = Release for OS operator
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MsgAckn1
Message acknowledgment status
1 (output STATUS of first
ALARM_8P)
WORD
16#0000
MsgAckn2
Message acknowledgment status
2 (output STATUS of first
ALARM_8P)
WORD
16#0000
MsgAckn3
Message acknowledgment status
3 (output STATUS of first
ALARM_8P)
WORD
16#0000
MsgErr1
Message error 1 (output ERROR
of first ALARM_8P)
BOOL
0
SIPART PS2 HART
7.1 SipPS2HA
SITRANS Library for PCS 7
230
Function Manual, 05/2019, A5E35351976-11