4
Corrected Volume flow
5
Fraction A
6
Fraction B
7
Fraction A %
8
Fraction B %
11
Totalizer 1
12
Totalizer 2
13
Totalizer 3
12.1.6
I/Os of SitrFC43
I/Os of SitrFC43
Input parameters
Parameter
Description
Type
Default
SlotHart
Slot number of the Lut400 within
the AI module in the ET 200M
from HW Config
INT
0
PV_In
Process value (4 to 20 mA signal) STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
PV
First HART variable (primary var‐
iable)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
SV
Second HART variable (secon‐
dary variable)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
TV
Third HART variable (tertiary var‐
iable)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
QV
Fourth HART variable (quaterna‐
ry variable)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
FbkDosVlv
Feedback from dosing valve
BOOL
0
LagTime
Delay time [s]
REAL
10.0
PV_OpScale
Limit for scale in PV bar graph of
faceplate
STRUCT
● High : REAL
● Low: REAL
-
● 100.0
● 0.0
SV_OpScale
Limit for scale SV
STRUCT
● High : REAL
● Low: REAL
-
● 100.0
● 0.0
SITRANS FC430
12.1 SitrFC43
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
481
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...