Reset totalizer to zero
The Totalizer 1 or 2 value is reset in the module by means of the interconnectable
parameter
ReTot1Li
or
ReTot2Li
. The reset is triggered by a 0 to 1 edge. You may also reset
the count values to zero using the standard view of the faceplate.
5.1.5
Mag6T dosing unit functions
The functions for this block are listed below.
Status diagram
The block provides the following states:
● "Start"
● "Pause"
● "Stop"
● "Off"
Status changes are initiated by the following commands:
● "Start"
● "Continue"
● "Pause"
● "Stop"
● "Dosing on/off"
"Dosing on" means that both dosing (
DOnLi
input) and the dosing screen form (
DOnMLi
input)
are switched on, i.e. are
TRUE
.
Dosing can only be started if the dosing setpoint is greater than zero and no interlock is active.
SITRANS F M MAG 6000
5.1 Mag6T
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
81