(24) Automatic preview
This display is only visible in "manual mode", in "local mode", or with a reset request in
"automatic mode", when the current output signals are not identical to the control in "automatic
mode".
The display shows what state the valve would assume if you switched from "manual" or "local"
mode to "automatic mode", or performed a reset to "automatic mode".
(25) Status display of the control valve
You can find additional information on this in section SipPS2PA block icon (Page 318).
8.1.8.3
Limit view of SipPS2PA
Several values can be set by default in this view:
● Manipulated variable difference limits
● Readback value limits
● Manipulated variable operating range
The toolbars of the faceplate and the block icon indicate when the limits are reached or violated.
SIPART PS2 PA
8.1 SipPS2PA
SITRANS Library for PCS 7
310
Function Manual, 05/2019, A5E35351976-11