4.5
Separate delay times for each alarm
Feature bit
Number of the
Feature
bit: 8
Separate delay times for each alarm
You can use this
Feature
bit to activate the alarm delay type "Two time values for each
individual limit".
The default setting is 0.
Bit = 0: The alarm delay type "Two time values for each individual limit" is deactivated.
Bit = 1: The alarm delay type "Two time values for each individual limit" is activated.
4.6
Activating the run time of feedback signals
Feature Bit
Number of the
Feature
bit: 11
Activating the run time of feedback signals
Use this
Feature
bit to activate the run time of feedback signals.
The default setting is 0.
Bit = 0: Deactivated: Tracking of feedback for simulation immediately after the trigger signal.
Bit = 1: Activated: Tracking of feedback for simulation after the trigger signal and expiration of
the monitoring time (
MonTiDynamic
). The feedback signals are generated after expiration of
the monitoring time.
4.7
Enabling bumpless switchover to automatic mode for valves, motors,
and dosers
Feature bit
Number of the
Feature
bit: 17
Bumpless switchover
You can use this
Feature
bit to enable the bumpless switchover from local/manual mode to
automatic mode.
Default setting is 0
Configurable response using the Feature I/O
4.7 Enabling bumpless switchover to automatic mode for valves, motors, and dosers
SITRANS Library for PCS 7
52
Function Manual, 05/2019, A5E35351976-11